Overview

CBS replaces field circuit breakers during interlock tests with protection panels and supports reclosing tests up to 765 kV.
- A circuit breaker simulator that verifies transmission line reclosing systems without operating the actual breaker
- A simulator linked to an analysis system that reviews operation before and after interlock tests, so test analysis runs automatically during testing
Applies technology transferred from KEPCO's Equipment Diagnosis Office / Field-tested by KEPCO's Equipment Diagnosis Office / Validated at the KEPCO Research Institute's protective relay test center
Why It Matters
Excessive breaker operation during testing produces metal particles that raise the risk of failures, so advanced countries strictly limit breaker operations during construction to 100–200 (e.g., 200 at UAE nuclear plants). In Korea, by contrast, there is no limit and breakers are operated excessively.
Current practice
- Actual breakers are operated directly during interlock tests of transmission line reclosing systems
- Interlock tests of other protection systems also operate actual breakers
Problems
- Breakers are operated repeatedly to verify reclosing systems and protective relay interlocks rather than the breaker itself, causing unnecessary operations
- Excessive operation during testing affects maintenance, shortens breaker life and can cause failures
- Reliability should be verified by freely changing breaker Trip and Open times, but this cannot be done effectively when controlling a real breaker
Key Advantages
- Freely configurable Trip Time and Close Time
- Interlock between test units to test both ends of the breaker at once
- Test unit and analysis system run together, while the test unit can also operate independently
- A breaker simulator with digital inputs and outputs that performs breaker functions for 154 kV, 345 kV and 765 kV
- A built-in analysis system reviews signal operation before and after simulation, so analysis runs during testing
Key Features
CBS hardware functions
- Supports 765 kV HSGS
- Breaker logic processing
- Signal output
- Single-line diagram display
- Trip / Close
- Breaker operating time setting
Analysis software functions
- Records operation results in COMTRADE format
- Sets delays for breaker Trip and Close and displays meter readings
- Receives and analyzes binary input and binary output signals
- Analyzes signal operation before and after simulation via the I/O module and displays the results

Expected Benefits
- Greatly reduces operation of real breakers, preventing failures and premature aging
- Removes harmful factors and lowers breaker maintenance costs
- Transmission line reclosing can be verified with minimal opening and closing of actual field breakers
- Real-time result analysis shortens root-cause analysis of failed interlock tests and enables accurate protection system verification
- Eliminates unnecessary waiting caused by drops in breaker hydraulic or air pressure during testing
- Reclosing systems can be verified without operating the breaker, cutting test time by 90% or more
Specifications
CBS product
| Power | DC 110~150V | ||
|---|---|---|---|
| Serial Port | MicroUSB 5-pin and Bluetooth | ||
| Binary Input | 12 Channel | ||
| Binary Output | 15 Channel | ||
| Status LED | 9-channel breaker status display | ||
| Trip/Close Button | 6 (2 per breaker) | ||
| Size | 270 X 210 X 123 (mm) | ||
CBS case
| External size | 411x321x165(mm) | ||
|---|---|---|---|
| Internal size | 372×257×153 (lid 28 + body 125) | ||
| Weight | 2.34kg | ||
| Waterproofing | Waterproof to 5 m, moisture-proof | ||
| Operating temperature | -40℃~80℃ | ||
| Material | Ultra-strong special fiber plastic for all-weather equipment protection | ||
| Color | Yellow | ||
Software
| OS | Windows 7 or later | ||
|---|---|---|---|
| SDK | .NET Framework 3.5, 4.0 | ||
| Resolution | 1920 X 1080 | ||
| Bluetooth | Bluetooth 2.0 or later | ||