KO EN

CBS

Circuit breaker simulator

Overview

CBS

CBS replaces field circuit breakers during interlock tests with protection panels and supports reclosing tests up to 765 kV.

  • A circuit breaker simulator that verifies transmission line reclosing systems without operating the actual breaker
  • A simulator linked to an analysis system that reviews operation before and after interlock tests, so test analysis runs automatically during testing

Applies technology transferred from KEPCO's Equipment Diagnosis Office / Field-tested by KEPCO's Equipment Diagnosis Office / Validated at the KEPCO Research Institute's protective relay test center

Why It Matters

Excessive breaker operation during testing produces metal particles that raise the risk of failures, so advanced countries strictly limit breaker operations during construction to 100–200 (e.g., 200 at UAE nuclear plants). In Korea, by contrast, there is no limit and breakers are operated excessively.

Current practice

  • Actual breakers are operated directly during interlock tests of transmission line reclosing systems
  • Interlock tests of other protection systems also operate actual breakers

Problems

  • Breakers are operated repeatedly to verify reclosing systems and protective relay interlocks rather than the breaker itself, causing unnecessary operations
  • Excessive operation during testing affects maintenance, shortens breaker life and can cause failures
  • Reliability should be verified by freely changing breaker Trip and Open times, but this cannot be done effectively when controlling a real breaker

Key Advantages

  • Freely configurable Trip Time and Close Time
  • Interlock between test units to test both ends of the breaker at once
  • Test unit and analysis system run together, while the test unit can also operate independently
  • A breaker simulator with digital inputs and outputs that performs breaker functions for 154 kV, 345 kV and 765 kV
  • A built-in analysis system reviews signal operation before and after simulation, so analysis runs during testing

Key Features

CBS hardware functions

  • Supports 765 kV HSGS
  • Breaker logic processing
  • Signal output
  • Single-line diagram display
  • Trip / Close
  • Breaker operating time setting

Analysis software functions

  • Records operation results in COMTRADE format
  • Sets delays for breaker Trip and Close and displays meter readings
  • Receives and analyzes binary input and binary output signals
  • Analyzes signal operation before and after simulation via the I/O module and displays the results

Expected Benefits

  • Greatly reduces operation of real breakers, preventing failures and premature aging
  • Removes harmful factors and lowers breaker maintenance costs
  • Transmission line reclosing can be verified with minimal opening and closing of actual field breakers
  • Real-time result analysis shortens root-cause analysis of failed interlock tests and enables accurate protection system verification
  • Eliminates unnecessary waiting caused by drops in breaker hydraulic or air pressure during testing
  • Reclosing systems can be verified without operating the breaker, cutting test time by 90% or more

Specifications

CBS product

CBS product specifications.
PowerDC 110~150V
Serial PortMicroUSB 5-pin and Bluetooth
Binary Input12 Channel
Binary Output15 Channel
Status LED9-channel breaker status display
Trip/Close Button6 (2 per breaker)
Size270 X 210 X 123 (mm)

CBS case

CBS case specifications.
External size411x321x165(mm)
Internal size372×257×153 (lid 28 + body 125)
Weight2.34kg
WaterproofingWaterproof to 5 m, moisture-proof
Operating temperature-40℃~80℃
MaterialUltra-strong special fiber plastic for all-weather equipment protection
ColorYellow

Software

CBS software specifications.
OSWindows 7 or later
SDK.NET Framework 3.5, 4.0
Resolution1920 X 1080
BluetoothBluetooth 2.0 or later